NEED OF GRADING CAPACITORS IN CIRCUIT BREAKERS IN EHV SYSTEM
The Grading capacitors are the capacitors (Typical value of around 500 Pico farads) which are positioned parallel with the interrupting units of the circuit breakers.
Before judging the necessity of grading capacitors, let us
discuss the importance of these capacitor units across interrupting unit of the
circuit breaker and what are the consequences of neglecting them.
What is the purpose of Grading Capacitors?
Let's examine a 400 kv Transmission line linking two substations via a circuit breaker at each end. The purpose of this transmission line is to facilitate the bidirectional power transfer between Busbars of these substations. Suppose if there is a grounded fault on this line (May be a single phase or two phase or three phase fault) somewhere between the two substations.The relays situated at both ends of the line will detect this fault and will trip the breakers accordingly.Now,with the breaker open,One end of the circuit breaker is grounded via the transmission line (due to fault),while the other end is connected to the bus via an isolator,as illustrated in the figure below.
Now the scenario is
Breaker is in open condition,One end of the Circuit breaker is grounded via
transmission line (due to fault) and the other end of the circuit breaker is
connected to the bus via an isolator as shown in the fig below.
It is clear from the derivation that there is an imbalance of voltage across two interrupter
units which is three fourth of Bus voltage across Interrupter-2 and one fourth
of voltage across Interrupter-1 Unit.Now,this creates the problem.The effective
voltage applied across the interrupting
units of the breaker should be same.
The solution to avoide this condition is by placing a
grading capacitors of comparatively large value
across two interrupting units due to which net capacitance of the two
interrupting units will be approximately equal (Because the capacitance of
interrupting units of the breaker were comparitively very small compared to the
Grading capacitors across it) and results in equal distribution of Bus voltage
across two interrupting units of the circuit breaker.
So basically necessity of Grading capacitor arises as the Open the contacts of the Circuit breaker (Two interrupting units ) will be applied with an voltage equal to Bus voltage across it via a bus isolator .Here the bus isolator is the culprit which connecting the Sub station bus to the Circuit breaker end.
What if we are able to disconnect that
Bus connection from the Circuit breaker Interrupter-1 (By opening the
Bus isolator) immediately after the
tripping of the circuit breaker due to fault.?
If we do so,
there will not be any voltage across the open contacts of the circuit breaker
and the there is no need of provision of
Grading capacitors .
We can
automate this opening of isolator Open coil after the tripping of Circuit
breaker due to fault by using the Auxillary switch contacts of the circuit
breaker.
Connection
of three auxillary switch contacts (Of different phases ) in series will avoide
Unnecessary opening of isolator due to single phase faults there by ensuring
smooth operation of the system during auto reclose operations.
It is better
to provide a delay of few milli seconds for the operation of isolator coil as
immediate opening of the isolator may creates huge sparking at the terminals of
the isolator.
It is highly suggestable to initiate the pulse for isolator after fully opening of circuit breaker contacts (Arc quenching will be completed in breaker itself).
By
B.S.N.Uday Kumar,
Engineer,NTPC Ltd.
Comments
Post a Comment